Abstract
The effective design of an energy efficient heating, ventilation and air conditioning system is reliant on multiple components. Among others, the air-handling unit cooling coil and its ability to perform efficiently directly influences heating, ventilation and air conditioning system performance. This paper investigates the energy and thermal performance of a water-cooled central cooling plant when combined with a direct evaporative cooling system located between the cooling tower and cooling coil of the air-handling unit. The evaporative cooler uses the water made by cooling tower to reduce the temperature of the 100% ambient air. The cooled air then passes through the cooling coil. This paper will demonstrate a series of mathematical models of the system components and validate them against experimental results. For this purpose, the central cooling plant is extensively equipped with a number of sensors and instrumentation devices for experimentation and data collection. The influence of the evaporative cooler on the energy saving potential and thermal comfort of the central cooling plant is evaluated. The advantages of this proposed hybrid system rests with the fact that the refrigeration effect of the chiller’s evaporator is decreased, which causes reduction of compressor power consumption. Results show that the hybrid system can provide average monthly energy savings between 11% and 24%, while enhancing the comfort level inside the building.