Abstract
Cleaning coils can be an efficient way to reduce the need for reparations and maintain the functionality of a ventilation system. This study builds upon existing knowledge concerning the contamination of heat exchangers. Through field measurements on coils and heat-recovery units, a laboratory experiment on a coil, and a generic calculation example, this study determines the impact of sustained contamination on heat-recovery units with regards to energy use. Field measurements made before and after cleaning of heat exchangers show an average increase in the pressure drop by 12% and decrease in the thermal exchange efficiency by 8.1% due to mass deposited on the surface of the heat exchangers. Results from a laboratory test show a correlation between the mass deposited on a coil and (1) the increase in pressure drop over the coil, as well as (2) a diminishing heat exchange. Accumulating contamination on heat-recovery units in residential and commercial buildings (over time) is then linked to increasing pressure drop and diminishing thermal efficiency. With models based on these links, energy loss over time is calculated based on a generic calculation example in a realistic scenario.