Abstract
A dynamic model of a hybrid hydronic heating system has been developed. The overall model consists of a boiler, a heat exchanger, a ground loop heat pump, a ground loop heat exchanger, baseboard heaters (convector–radiators), and radiant floor hydraulic piping system. Two control strategies for improving the overall system performance were explored: (1) a conventional proportional-integral (PI) control and (2) an adaptive gain control. The simulation results showed that the performance of the adaptive controller is better than the fixed gain PI controller in disturbance rejection and stability. Energy simulations under three different operating strategies were conducted: (1) a fixed set-point PI control, (2) an outdoor air temperature reset control, and (3) an optimal set-point adaptive PI control. It was shown that the outdoor temperature reset strategy can save 4.5 and 19.9% energy under cold day and mild day conditions compared to the fixed set-point PI control strategy. The optimal adaptive PI control strategy resulted in higher energy savings of 6.6 and 22% as compared to the PI control under cold and mild day conditions, respectively.