Abstract
A study of 14 open-plan offices equipped with occupant controlled general lighting recorded achieved workstation lighting conditions at a number of times of the year. The results confirmed the occurrence of a wide range of workstation lighting levels, many significantly below CIBSE Code recommendations, with average electrical loadings due to lighting in the order of 55% of maximum. System con-figuration had a significant influence on luminaire output, illuminances and energy consumption. In general the lowest luminaire outputs were in buildings where the default reset level was to a low output, with the highest outputs being in buildings having high reset levels and large control groups. In addition locally sited control devices were associated with lower luminaire output.