Abstract
The Westend Bridge is located on the A100 Highway in Berlin. An integrated continuous dynamic monitoring system, composed of 20 velocity sensors, 5 temperature sensors, 3 strain gauges, 2 inclination sensors and 1 crack sensor was implemented by the Federal Institute for Materials Research and Testing (BAM) in 2000. The system runs continuously with occasional intermittence and leads to a huge amount of data over a 14-year span. In this article, variations of the strain, crack and inclination measurements during the last 14 years are presented. It is noted that the observed crack and inclination of the bridge are strongly influenced by seasonal temperature variation. It further induces change in the relationship between the strains measured in both concrete and prestressed tendon. Application of