Abstract
It is common for sprinkler heads in residential buildings to be of the concealed type. Key parameters for the thermal sensitivity of sprinkler heads are the response time index (m½s½) and conductivity factor (C factor, m½s−½). BS 9252:2011 and BS EN 12259-14:2020 outline test methods to determine whether sprinkler heads achieve adequate thermal sensitivity, stipulating that a room test be undertaken for concealed heads. In carrying out this test, neither the response time index nor C factor is defined. This paper uses computational modelling tools Fire Dynamics Simulator and B-RISK to simulate the room test. In running these simulations, maximum values for the ‘effective’ response time index and C factor needed to pass the room test can be estimated, assuming concealed heads can be represented as equivalent pendent heads. Initial deterministic simulations are used to calibrate results between Fire Dynamics Simulator and B-RISK. Monte Carlo modelling is then utilised within B-RISK, with variable parameters for the response time index and C factor (C), to estimate the relationship between the two parameters necessary to pass the room test. As a result, it is proposed that this relationship can be represented using a simple, empirical power law equation of response time index = 100 (5.4–C)2/3, where C < 5.4.