Abstract
The liquid desiccant enthalpy recovery is an efficient way to save energy in air-conditioning systems. In this study, a counter-flow liquid desiccant enthalpy recovery device was proposed and experimentally analyzed. Enthalpy transfer capacity, enthalpy efficiency and pressure drop per height of packing were used as indices to describe its performances. Based on the experiment results, the heat and mass transfer model of a packed tower was used to simulate and optimize the performance of this device. The maximum enthalpy efficiency and enthalpy transfer capacity were achieved when the optimal air velocity (1.9–2.1 m/s in this study) maintained to be slightly below the air velocity at the loading point and the thermal capacity ratio of air to desiccant (m*) equaled to 1. These conclusions are valuable to both design and operation of such an enthalpy recovery device.