Abstract
It is estimated that in the UK, 200,000 residents live in park and holiday homes all year round, the majority of which are elderly and on low incomes. As these homes are often thermally inefficient and leaky, these residents are some of the most susceptible in society to fuel poverty. Despite this, there is a dearth of empirical data available on the in situ fabric performance of these homes. This paper presents the results obtained from undertaking a series of pressurisation tests and leakage identification on new build holiday homes. While the sample size reported is small, the results indicate almost a factor of two variation in the airtightness performance of the homes. In spite of this, all of the homes achieved an air permeability significantly lower than the default value incorporated within the industry standard Energy Efficiency Rating Calculator, suggesting that a much lower figure may be more appropriate. The results also suggest that the use of the air permeability metric within the calculator potentially biases the performance of holiday homes due to their particular form factor, and that this bias could be mitigated against by adopting the air leakage metric within any future revisions to the calculator.