Abstract
This study aims to present the fundamentals in which operation of a 100% outdoor air system integrates with indirect and direct evaporative cooling systems and to estimate its energy saving potential. The simulation of the proposed system is performed using a commercial equation solver program, and the annual operation energy saving potential with respect to a conventional variable air volume system is determined. This paper shows that significant operation energy savings (i.e. 21–51% less energy consumption) is possible principally by the pre-conditioning of supply air due to the waste heat recovery using the indirect evaporative cooler and the sensible heat exchanger units. By components, the proposed system shows a 16–25% less annual cooling coil load and an 80–87% reduced annual heating coil load with respect to the conventional variable air volume system, while there is no fan energy savings expected.