When attempting to reduce lead solubility by lowering the finished water pH in Providence, RI, from ∼10.3 to 9.7, consumer red water complaints and overall lead levels increased, prompting bench-scale tests and intensive field sampling into possible associations between higher particulate iron and particulate lead. At pH 10.3, iron release to water was as much as 35% lower in bench-scale tests and 99% lower in field samples compared with pH 9.7. Lower levels of particulate iron released at higher pH, translated to lower levels of particulate lead release after contacting downstream plumbing in bench testing. Although a significant decrease in distribution system iron at pH 10.3 did not immediately translate to decreased lead levels at all field sampling sites, complementary laboratory and field studies demonstrate that lead corrosion control is sometimes strongly linked to iron corrosion control.
Get full access to this article
View all access options for this article.
References
Supplementary Material
Please find the following supplemental material available below.
For Open Access articles published under a Creative Commons License, all supplemental material carries the same license as the article it is associated with.
For non-Open Access articles published, all supplemental material carries a non-exclusive license, and permission requests for re-use of supplemental material or any part of supplemental material shall be sent directly to the copyright owner as specified in the copyright notice associated with the article.